| THE CITY OF NORFOLK MODIFICATIONS TO HRPDC REGIONAL STANDARDS, 4th Edition | ||||||||||
| Section | Sub-Section | Name | Add/ Delete |
Modification | ||||||
| All Sections | Measurement for Payment. | Replace | See Appendix D for City of Norfolk Department of Utilities Measurement and Payment Item Descriptions. Replace all references to Mesaurement for Payment in the technical specifications with Appendix D. | |||||||
| 102 | VII | Standard Bid Items and Units | Delete | Use City of Norfolk Measurement and Payment descriptions. Refer to Appendix D. | ||||||
| All 100 sections | General Provisions | Replace | Revise all HRPDC General Provisions with Norfolk City Modifications and Department of Utilities Modifications | |||||||
| 200 | II.2.2 | Quality Assurance | Add | International Plumbing Code Norfolk Arboricultural Specifications and Standard Practice Manual | ||||||
| III.3.2 | Submittals | Modify | In first line delete letter “r” from word “manufacturer”. | |||||||
| III.3.6 | Submittals | Add | Add the following sentences: “Requests for substitutions shall be submitted at the pre-construction meeting and must be approved in writing by the Engineer prior to the start of any construction.” | |||||||
| V.5.1.C | Aggregate | Add | Insert “of this document” after “Division 8 activities” and before the comma. | |||||||
| V.5.10.A.2 | Casing Pipe | Modify | In second line after word “be” add word “in”. | |||||||
| V.5.10.A.9 | Ductile Iron Pipe | Add | Ductile Iron pipe shall have Sewpercoat calcium aluminate lining, Protecto 401 ceramic epoxy lining, or equal hydrogen sulfide resistant lining approved by the Department. | |||||||
| V.10.B.5 | PVC Pipe | Modify | Correct the second sentence to read: “When Compact fittings are used, they shall have a minimum acceptable pressure rating of 350 psi.” | |||||||
| V. 5.10.D. | HDPE Pipe | Add | HDPE pipe may only be used with prior written approval by the Department. | |||||||
| V.5.10.E.1.a. | Valves | Add | All gate valves for sewer shall open left (counterclockwise). | |||||||
| V.5.10.E.1.c. | Valves | Delete | Delete “with threaded connections” from the first sentence. | |||||||
| V.5.10.E.1.d. | Valves | Add | Accessories: Provide zinc plated bonnet bolts, studs and nuts for unsubmerged service. Provide stainless bonnet bolts, studs and nuts for submerged service. Make wedging devices bronze to iron or bronze to bronze. Provide glands which are bronze or bronze bushed and bronze gland bolts and nuts. | |||||||
| V.5.10.E.3 | Valve Operators | Delete | “A valve key wrench of adequate length and of each type required shall be provided for each project.” | |||||||
| V.5.10.E.4. | Valve Stem Extensions | Delete | Strike out section | |||||||
| 200 | V.5.10.E.5. | Check Valves | Add | Provide single disc swing check valves designed to allow a full diameter passage and to operate with a minimum loss of pressure. Provide 1/8 through 3 inch check valves that meet the requirements of MSS SP-80. Provide 4 inch through 24 inch check valves that meet the requirements of AWWA C508. Equip check valves with bronze renewable seat rings, bronze discs or disc rings and bronze disc hinge bushings and pins. Carefully mount discs and provide discs that swivel in disc hinges. Provide pins, discs and other parts that are noncorrosive, nonsticking and properly cured to operate satisfactorily within a temperature range of 34 to 100 degrees Farenheit and with the fluids specified. Equip 6 inch and larger check valves with outside levers and weights. Provide check valves manufactured by American Flow Control, Clow Valve, M&H Valve, Mueller Valve, or approved equal. | ||||||
| V.5.10.G.3.c | Joint Restraint Devices | Add | Harnessing: For ductile-iron pipe and fittings with mechanical joints that require harnessing, provide ductile-iron mechanical joint retainer glands. | |||||||
| V.5.10.G.4.c | Joint Restraint Devices | Add | Harnessing: For PVC joints requiring harnessing, provide Series 1300/1390 restraining fittings as manufactured by Uni-flange, Corp., Series 1110 HV and Series 2000 PV as manufactured by EBAA Iron Sales, Inc., or equal. | |||||||
| V.5.10.G.5.a | Joint Restraint Devices | Modify | After word “accordance” add word “with”. | |||||||
| V.5.11.A.5 | Ductile Iron Pipe Fittings | Modify | Correct the second sentence to read: “When Compact fittings are used, they shall have a minimum acceptable pressure rating of 350 psi.” | |||||||
| V.5.11.A.8 | Ductile Iron Pipe Fittings | Add | After ANSI/AWWA add “Current department approved linings include Sewpercoat calcium aluminate lining and Protecto 401 ceramic epoxy lining. Other hydrogen sulfide resistant linings shall be submitted for review and approval as equal”. | |||||||
| V.5.11.B.8 | PVC Pipe Fittings | Add | Add paragraph “For Mains installed, where cover is 10’ (ten feet) or greater, the pipe shall be C900/C905 DR 18 or Ductile Iron.” | |||||||
| V.5.11.B.9 | PVC Pipe Fittings | Add | Add paragraph “All fittings shall be molded or ductile iron. No fabricated fittings will be allowed.” | |||||||
| V.5.11.C. | ABS or PVC Composite Pipe and Fittings | Delete | Strike out section | |||||||
| V.5.19.A.5 | Ductile Iron Pipe fittings | Modify | Correct the second sentence to read: " When Compact fittings are used, they shall have a minimum acceptable pressure rating of 350 psi." | |||||||
| V.5.19.B.3. | PVC Pipe | Delete | “couplings, and fabricated fittings” and “or fitting”. | |||||||
| V.5.19.B.6 | PVC Pipe | Add | Add as the final sentence in the paragraph: "Where Schedule 80 PVC is used, solvent cement shall meet the requirement of ASTM D-2564." | |||||||
| V.5.19.B.7. | PVC Pipe | Delete | Strike out paragraph | |||||||
| V.5.19.E | Copper Water Pipe | Delete | Strike the sentence that starts, “Fittings shall be wrought…” | |||||||
| V.5.19.F.1.c. | Valves | Delete | Strike out “with threaded connections”. | |||||||
| V.5.19.F.1.d. | Valves | Add | All gate valves for water shall open right (clockwise). | |||||||
| V.5.19.F.2.a | Butterfly Valves | Modify | Replace “16 inches” with “20 inches”. | |||||||
| 200 | V.5.19.F.4. | Valve Operators | Modify | Strike out the sentence that begins, “A valve key wrench…” Add the following: “NOTE: Water valves open right (clockwise).” | ||||||
| V.5.19.F.5. | Valve Stem Extensions | Delete | Strike out paragraph | |||||||
| V.5.19.H.2. | Fire Hydrants | Delete | "The fire hydrant shall be painted with a high gloss, alkalyd industrial enamel (colors to be selected by Owner)". | |||||||
| V.5.19.H.3 | Fire Hydrants | Delete | Strike out paragraph | |||||||
| V.5.19.H.6 | Fire Hydrants | Delete | Strike out paragraph | |||||||
| V.5.19.H.7 | Fire Hydrants | Add | "All fire hydrants shall be manufactured in complete accordance with American Water Works Association Specification C502, latest revised edition, and shall be as manufactured by the Darling Valve & Manufacturing Company (Model B-50-B), Mueller Centurian A-421, Pacer Model W-67, Kennedy K-81, or approved equal. Hydrants shall have full 360 degree revolving heads and shall open by turning the operating nut to the right (clockwise). | |||||||
| V.5.19.I.5 | Service Saddle | Modify | In first sentence insert word “main” after word “water”. | |||||||
| V.5.19.J.1 | Water Meters | Delete | “meter yoke”. | |||||||
| V.5.19.K.4.a. | Concrete Reaction Blocking | Add | Add the phrase, ", or as designated by the Engineer," after the word, "Drawings". | |||||||
| V.5.19.K.4 | Concrete Reaction Blocking | Delete | subsections b and c | |||||||
| V.5.19.L.2. | Tapping Valves and Sleeves | Delete | Strike out the sentence, “The valves shall be subjected to a factory test…” | |||||||
| V.5.19.L.3.a. | Tapping Sleeves for DI Pipe and PVC C-900 | Modify | In the first sentence insert “full bodied” between “shall be” and “mechanical joint”. Delete “in accordance with ANSI/AWWA C110/A21.10. and” from the sentence beginning with “Tapping sleeves shall be…” | |||||||
| V.5.19.L.3.b. | PVC pipe (Other than C-900) | Delete | Strike out the first paragraph, which begins, “Tapping sleeves shall be complete…” | |||||||
| V.5.20.B. | Subsurface Utility Warning Tape | Modify | Replace “metalized” with “non-metallic”. | |||||||
| V.5.21.B.6.d | Wall Thickness | Modify | Last word in 6th line should be “of” instead of “or”. | |||||||
| V.5.21.F.1 | Manhole Rehabilitation Using Cementious Products | Delete | Delete entire section | |||||||
| V.5.21.I.2 | Manhole Frame Seals | Delete | After "only be installed with" delete " the cementious lining and" | |||||||
| 303 | II.2.2.B.5 | Trenching, Backfilling, and Compaction | Modify | Re-write the last sentence to read ”In such instances, sheeting will be cut off at least two (2) feet below finished grade and left in place.” | ||||||
| 303 | II.2.2.E.1 | Trench Bedding and Backfilling | Modify | Replace “Contractor” with “Inspector”. | ||||||
| II.2.2.E.4. | Trench Bedding and Backfilling | Modify | Replace the paragraph with: “Backfill material shall be solidly compacted around the pipe in 6” layers up to sub-base of the roadway or the existing ground elevation. As a minimum, compact each layer of the backfill material to 95% maximum density as determined in accordance with VTM-1. | |||||||
| II.2.2.E.7. | Trench Bedding and Backfilling | Modify | Replace in the first sentence, "...material to not less than the following percentages at the maximum…" with "…material to 95% maximum…". | |||||||
| II.2.2.E.7. | Trench Bedding and Backfilling | Delete | sub sections “a – c”. | |||||||
| II.2.2.E.7.e. | Trench Bedding and Backfilling | Add | “The City may, at any time, require compaction testing to ensure compliance with the specifications. A recognized testing laboratory that is selected by the City will conduct all tests. The testing laboratory is to be qualified in the field of the materials to be tested. If applicable, all tests will be conducted in accordance with V.D.O.T.’S “Manual for Virginia Testing Methods” (Current Edition, as Revised). Payment for all tests will be in accordance with the following: A) The cost of all tests failing to meet the minimum requirements will be borne by the Contractor. B) The costs of all tests that either meet or exceed the minimum requirements shall be borne by the City. | |||||||
| II.2.2.G.2. | Pavement Removal for Placement of Pipelines | Modify | Replace the sentence beginning with “The minimum requirements for a ….” with ”Temporary paving shall be installed and maintained to provide a suitable driving surface on residential streets. Contractor shall allay dust. Daily temporary pavement may be recycled asphalt, crushed concrete, cold mix asphalt patch or VDOT 21A Stone. The inspector has the final decision of the acceptability of temporary paving”. This item shall be included in the L.F. cost of the main. | |||||||
| II.2.3. | Tolerances | Delete | Complete Section | |||||||
| 801 | II.2.2.C.7. | Pipe Installation | Modify | Replace “300” with “100” | ||||||
| II.2.2.F. | Tracer Wire | Modify | Replace “attached every 10 feet to” with “1 foot above”. | |||||||
| II.2.2.G. | Subsurface Utility Tape | Modify | Re-write the paragraph to read,” All non-metallic water mains shall be identified by a subsurface non-metallic utility warning tape placed at an elevation of 12” above the copper tracer wire or as directed by the owner, conforming to Section 200.” | |||||||
| II.2.3.A. | Valve Installation | Modify | After “direction of openings” insert the following, “(All water valves open right)”. Re-write the second sentence to read, ”Valves found not opening to the right, or determined to be defective by the Owner shall be rejected, removed from the site, and replaced by the Contractor at no additional cost to the Owner.” | |||||||
| II.2.6.C. | Restraint | Add | After “…coating” add the following, “or as directed by the Owner.” | |||||||
| II.2.7.C. | Connections to Existing Mains | Delete | Delete the sentence that begins with, “Connection shall be…”. | |||||||
| II.2.7.F.4 | Connections to Existing Mains | Modify | Replace the paragraph with, "Tie-ins to existing mains shall only be performed after the new main has been satisfactorily pressure tested and chlorinated. The contractor may not tie-in the new main to the existing main until after the results of the bacteriological tests have been completed and approved by the owner." | |||||||
| 801 | II.2.7.G. | Tapping Existing Mains Under Pressure | Delete | Delete subsections 3,4, and 6. | ||||||
| II.2.7.G.5. | Tapping Existing Mains Under Pressure | Modify | Change the sentence to read, "Pressure shall be maintained for one (1) hour period without evidence of leakage." | |||||||
| II.2.7.G.7. | Tapping Existing Mains Under Pressure | Add | In the first sentence, after “…branch are acceptable” add the following, “unless otherwise directed by the Owner.” | |||||||
| II.2.8.B.1. | Pressure Test | Modify | In the sentence which begins, “Water mains shall be…” remove the portion that states, “1.5 times the expected working pressure or” and the portion that states, “,whichever is greater”. | |||||||
| II.2.8.B.3. | Pressure Test | Add | “, or as directed by the Owner.” | |||||||
| II.2.8.B.8. | Pressure Test | Modify | Replace this subsection with, “The test pressure shall be maintained at the pressure stated in the project specifications throughout the duration of the test period. The water used to maintain the test pressure shall be measured and shall be less than the allowable leakage in order for the main to have passed the test.” | |||||||
| II.2.8.B.10. | Pressure Test | Modify | After “…restraint and support” insert “ for testing apparatus”. | |||||||
| II.2.8.C.2. | Leakage Test | Modify | Insert the word “excess” between “…until the” and “leakage.” | |||||||
| 802 | II.2.1.E. | General | Add | Provide cut sheets for all manholes, 100 ft. stations and end-of-line cleanouts. | ||||||
| II.2.1.F. | General | Add | All Services which are reconnected to the replaced sewer main shall be shown on the "As Built" drawings with the exact distance from the nearest manhole and with the details of the method of reconnection. | |||||||
| II.2.2.C.4. | Pipe Laying | Add | "If a swab is in the pipe for cleaning, the grade shall be checked and recorded for each joint of pipe. | |||||||
| II.2.2.C.6 | Pipe Laying | Modify | After"…shall be closed" insert " by use of a temporary bulkhead" and delete " to the satisfaction of the Owner". | |||||||
| II.2.2.D.1. | Alignment and Grade | Modify | Replace "Drawings" with "approved laying schedule". | |||||||
| II.2.2.D.2. | Alignment and Grade | Delete | Entire subsection | |||||||
| II.2.3.B. | Manhole Installation | Add | To the end of the second sentence after: non-shrink grout-"and coated to match surfaces of manholes." | |||||||
| II.2.4.A.2. | Testing and Inspection | Modify | Change the sentence to read, "The Contractor shall submit to the Owner, at least 48 hours in advance, any requests to schedule testing and inspection." | |||||||
| II.2.4.B.1.a. (5). | Pipe Testing - Gravity Lines | Add | "Contractor is responsible for uncovering and restoring spot check sites at no additional cost to the Owner." | |||||||
| II.2.4.B.1.a. (8) | Pipe Testing - Gravity Lines | Modify | Replace the last sentence with, "See Section 811." | |||||||
| II.2.4.B.1.c.2.d | Remote Camera / TV Inspection | Modify | Bottom of page “d” should be (3). Paragraph at top of page – In second line change word “one” to “line”. | |||||||
| 802 | II.2.5.B | Connections | Modify | In parentheses should read (where stubs are bricked up or openings do not exist). | ||||||
| II.2.5.B | Connections | Modify | In third line change to Final Completion. | |||||||
| 803 | II.2.2.F | Tracer Wire | Modify | Replace "attached every 10 feet to" with " 1 foot above". | ||||||
| II.2.2.G | Subsurface Utility Tape | Modify | Re-write the paragraph to read "All non-metallic water mains shall be identified by a subsurface non-metallic utility warning tape placed at an elevation of 12" above the copper tracer wire or as directed by the Owner, conforming to Section 200." | |||||||
| II.2.3.A | Valve Installation | Modify | After "direction of openings" insert the following; "(All sanitary sewer valves open left)". Re-write the second sentence to read "Valves found not opening to the left, or determined to be defective by the Owner shall be rejected, removed from the site, and replaced by the Contractor at no additional cost to the Owner." | |||||||
| II.2.6.5.J.11 | Offsets to Existing Force Main | Modify | In third line, replace water main with force main. | |||||||
| 804 | II.2.1.D | Boring and Jacking execution | Modify | In second line delete “r” from word manufacturer. Change word “or” to “of”. | ||||||
| 805 | I.1.2.B.2 | Unusual Conditions | Modify | Replace the second half of the sentence that begins, “pressure tested in place…” and ends “…and tested in place.” with, “, and meets current Virginia Department of Health Sewage Collection and Treatment Regulations.” | ||||||
| 810 | II.2.2.F.3 | Acceptance of Cleaning Operation | Add | A television inspection shall be completed after cleaning to verify that the cleaning operation was successful. The television inspection shall be in accordance with Section 811 - Television Inspection. | ||||||
| 811 | I.1.2.A. | Submittals | Add | "Video Tapes shall be Extra High Grade T-120 VHS videotape for all television surveys. All taping shall be performed as SP (Standard Play, 2hrs/tape). All video shall be submitted to the Owner and will become the property of the Owner. Two labels are requried, with one label placed on the video and the other on the container. Permanently label each video with the following information: Owner Name, Contractor Name, Tape No., Date Televised, Date Submitted, Project Name, Branch Name, Street Name; Manhole No. From, Manhole No. To, Pipe Diameter, Pipe Length, Street Name." | ||||||
| I.1.2.D. | Submittals | Add | Overflow Prevention Plan | |||||||
| I.1.2.E. | Submittals | Add | Overflow Containment and Cleanup Plan | |||||||
| II.2.1.B.1. | Equipment | Add | Sewer scanner and evaluation technology, similar to the Blackhawk pipeline assessment system, is an acceptable alternative to CCTV. | |||||||
| II.2.2.A.2. | Flow Control | Modify | The end of the last sentence to read, "…unless approved by the Owner in advance". | |||||||
| 812 | I.1.2.P. | Submittals | Add | Overflow Prevention Plan | ||||||
| I.1.2.Q. | Submittals | Add | Overflow Containment and Cleanup Plan | |||||||
| Standard Details | RC_02 | Utility Locations | Delete | |||||||
| EW_02 | Payment Limits Trench Excavation and Backfill | Delete | ||||||||
| EW_03 | Trench Width Detail for Payment of Contingent Items | Delete | ||||||||
| CI_08 | Residential Entrance w/out Curb and Gutter | Delete | Use Norfolk Public Works/Codes Standard Driveway Entrance Detail | |||||||
| WD-01 | Dual Service Connection | Delete | Dual Service connection not allowed. | |||||||
| WD_02 | Water Service Installation Detail | Replace | Use the Norfolk Standard Detail for Typical Tap Installatioin, CW 01 | |||||||
| WD-03 | Water Meter Box (Type I) | Replace | Use the Norfolk Standard Detail for Water Meter Box & Cover, CW 02 | |||||||
| WD_04 | Water Meter Box (Type II) | Delete | ||||||||
| WD_05 | Blow Off Assembly | Replace | Use the Norfolk Standard Detail for Air Vent/ Blow-Off Valve, CWS 03 | |||||||
| WD_06 | Fire Hydrant Setting (TypeI) | Replace | Use the Norfolk Standard Detail for Fire Hydrant Installation, CW 04 and Fire Hydrant Connection, CW 05. | |||||||
| WD _07 | Fire Hydrant Setting (Type II) | Delete | ||||||||
| WD _08 | Fire Hydrant Setting (Type II) | Delete | ||||||||
| WD_09 | Temporary Manifold For Test and Chlorination | Delete | ||||||||
| WD_10 | Precast Concrete Vault - Non-Load Bearing | Delete | ||||||||
| WD_11 | Precast Concrete Vault - H20 Loading | Delete | ||||||||
| WD_12 | Metal Meter Vault | Delete | ||||||||
| WS _01 | Standard Valve Box Frame and Cover | Delete | Use the Norfolk Standard Detail for Large Valve Box Frame and Cover, CWS 01 and CWS 02 for Small Valve Box Frame and Cover. | |||||||
| WS _02 | Valve Setting Detail | Delete | ||||||||
| WS _03 | Manual Air Vent Assembly | Replace | Use the Norfolk Standard Detail for Air Vent/ Blow-Off Valve, CWS 03 | |||||||
| WS_04 | Steel Casing Detail | Replace | Use the Norfolk Standard Detail for Water Line Casing, CWS 07A and CWS 07B | |||||||
| WS _05 | Standard Thrust Blocks | Delete | ||||||||
| WS _06 | Obstruction By-Pass Uniform Offset | Delete | ||||||||
| WS _07 | Restraining Rod Detail | Delete | ||||||||
| SS_01 | Standard Precast Concrete Manhole w/Extended Monolithic Base | Replace | Use Norfolk Standard Detail for Standard Precast Sewer Manhole, CS 03 | |||||||
| SS_02 | Precast Concrete Shallow Manhole | Replace | Use Norfolk Standard Detail for Shallow Precast Sewer Manhole, CS 04 | |||||||
| SS_03 | Sanitary Sewer Straddle Manhole | Delete | ||||||||
| SS_04 | Sanitary Sewer Interior Drop Manhole | Replace | Use Norfolk Standard Detail for Standard Precast Sewer Drop Manhole, CS 05 | |||||||
| SS_05 | Sanitary Sewer Exterior Drop Manhole (For Existing Manhole Only) | Replace | Use the Norfolk Standard Detail for Standard D.I. Drop Connection for Existing Brick Manhole, CS 01 | |||||||
| SS_06 | Sanitary Sewer Manhole Adjustment | Delete | ||||||||
| SS_07 | Sanitary Sewer Manhole Invert Shaping | Delete | ||||||||
| SS_08 | Connection into Existing Manhole | Delete | ||||||||
| SS_09 | Sanitary Sewer Manhole Casting (24") | Delete | ||||||||
| SS_10 | Sanitary Sewr Manhole Cover (24") | Delete | ||||||||
| SS_11 | Saniary Service Lateral Clean Out Frame and Cover | Replace | Use Norfolk Standard Detail for Mainlline Cleanout Casting and Cover, CS 10 | |||||||
| SS_12 | Sanitary Service Lateral Clean Out Frame and Cover For Heavy Loads | Delete | ||||||||
| SS_13 | Sanitary Sewer Main Line Clean Out Box | Replace | Use Norfolk Standard Detail for Mainlline Cleanout Casting and Cover, CS 10 | |||||||
| SS_14 | Sanitary Sewer Service Connection | Replace | Use Norfolk Standard Detail for Typical Wye/Lateral Layout and Property Line Cleanout, CS 11 | |||||||
| SS_15 | Dual Sanitary Sewer Service Connections | Delete | Dual Service connection not allowed. | |||||||
| SS_16 | Deep Sanitary Sewer Service Connection | Delete | ||||||||
| SS_17 | Force Main Saxophone | Replace | Use the Norfolk Standard Detail for Force Main Saxophone, CS 14 | |||||||
| SS_18 | Force Main to HRSD Force Main | Delete | ||||||||